Flame Arrestors prevent the passage of flames in storage vessels and along associated pipework systems and have applications in a wide range of industries including petroleum and petrochemicals, gas, marine and sewage treatment.
Flame Arrestors
Request a Quote
 
Download PDF
INSTALLATION
 
Series 8350 Flame Arrestors should be mounted with the axis vertical and as close as possible to the potential source of ignition. Series 8360 Flame Arrestors have been designed for fitting to the down-turned end of free vent pipes.
 
CONSTRUCTION
 
Series 8350 Flame Arrestor consists of a tube bank made up of spirally wound alternate layers of flat and corrugated stainless steel sheets, built around a solid core. The tube bank offers a multiplicity of small holes parallel to the line of flow. The tube element is retained between two flanged end sections and contained within an outer shell. (See Fig.1) Flame Arrestor can be fitted with a weather hood. (See Fig.2)
 
FEATURES
 
Crimped Ribbon Element Design
The corrugated crimped ribbon design of the Series 8350 Flame Arrestor element enables it to be manufactured to very close tolerances and hence can be efficiently size selected to suit the widest range of applications and flow parameters. Pressure drop across the Flame Arrestor is very low and hence it is suitable for high gas flow rates.
OPTIONS AVAILABLE
Weather Hood
Weather hoods are available for fitting to all sizes of Flame Arrestors, for use where the arrestors are mounted in exposed position, e.g. on vessel roofs
SIZING AND SELECTION
Due to varying degrees of hazard, it is necessary to very carefully assess the type and capacity of Flame Arrestor required for safe operation. A detailed application form, as specified within this catalogue, should be completed for every proposed Flame Arrestor application and returned to us to assist in the correct sizing of the Flame Arrestor required to suit each application.
SPECIFICATIONS
Sizes : 50 mm (2") 80 mm (3") 100 mm (4") 150 mm (6") 200 mm (8") 250 mm (10") 300 mm (12")
End Connections : ASA 150 FF
FLAME ARRESTOR
SERIES 8350
 
flame-arrestor
flame-arrestor
flame-arrestor
flame-arrestor
 
 
flame-arrestor
 
MATERIALS OF CONSTRUCTION
• Body : Aluminium alloy LM-25
• Shell : Aluminium alloy LM-25
• Core Tube : Aluminium
• Tube Bank : Stainless Steel AISI 304
• Hood : Galvanised Steel
• Hardware : Mild Steel (Optional) (Zinc Plated / Yellow Passivated)
APPLICATION DATA - IMPORTANT CRITERIA FOR SIZING SELECTION
Due to varying degrees of hazard, it is necessary to very carefully assess the type and capacity of Flame Arrestor required for safe operation. A detailed application form, to include information as listed below, should be completed and returned to us for each and every proposed Flame Arrestor application to assist in the correct sizing of the Flame Arrestor required to suit each application.
1. Enquiry / order number
2. Analysis of gases and/or vapours - % by volume or tank contents
3. Flash point
4. Storage tank capacity (if applicable)
5. Max. filling and emptying rates for storage tanks
6. Max. static pressure at Flame Arrestor
7. Max. temperature at Flame Arrestor
8. Min. temperature at Flame Arrester
9. Max. rate of flow (by volume)
10. Acceptable pressure drop
11. In-line or End-of-line type
12. If In-line type, distance of Flame Arrester from source of ignition
13. Type and size of flange or threads
14. Material for housing
15. Material for element
16. Advise if continuous burning on element possible
17. Special requirements (if any)